++++General
Farady Powertech strives to bring our customers the latest technology and competitive pricing and best service for pole mounted Auto circuit recloser
The FAR series Auto circuit recloser can use on overhead distribution lines as well as distribution substation applications for all voltage classes 11kV up to 38kV at 50/60HZ power system. And its rated current can reach 1600A.
The FAR series Auto circuit recloser integrates the functions of control, protection, measurement,communication,fault detection,on-line monitoring of closing or opening.comply to IEC62271 and ANSI/IEEE C37.60 standard
++++Service environment
a) Air temperature: Maximum temperature: +85ºC; Minimum temperature:-45ºC
b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level: Maximum installation altitude: 2500m or more higher.
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake
++++Technical data
No. | Item | Unit | data | |||
1 | Rated voltage | kV | 15 | 27 | 38 | |
2 | Rated current | A | 630 | 1250 | 1600 | |
3 | Rated frequency | HZ | 50/60 | |||
4 | Power frequency 1min | Dry | kV | 50 | 65 | 85 |
Wet | 45 | 55 | 75 | |||
5 | Lightning impulse withstand voltage(peak value)alternate, opposite/fracture | kV | 110 | 150 | 170 | |
6 | Rated short circuit breaking current | kA | 20 | 16/25 | 12.5 | |
7 | Rated short current switching current(peak value) | kA | 50 | 40/63 | 31.5 | |
8 | Rated peak value withstand current | kA | 50 | 40/63 | 31.5 | |
9 | 4S short time withstand current | kA | 20 | 16/25 | 12.5 | |
10 | Rated operating circulate | O-T1-CO-T2-CO-T3-CO-T4-CO | ||||
11 | Breaking current frequency under rated short circuit | times | 30 | |||
12 | Mechanism life | times | 10000 | |||
13 | Secondary loop 1 min power frequency withstand voltage | kV | 2 |